Warehouse Type Sprinklers | Heartz Bangla Ltd.

Warehouse Type Sprinklers

//Warehouse Type Sprinklers

Warehouse Type Sprinklers

Warehouse Type Sprinklers

Warehouse Type Spinklers are sprinklers designed for high and mass storage purposes with shelves for special applications. These sprinklers; According to their models, they give more water or more water to the effect area at low pressure. ESFR sprinklers are not required to use spinkler between shelf if their pressure is adjusted correctly according to their height.

Intermediate level sprinklers are developed sprinkler models for shelving between shelves and shelves. The only important point to be considered in the use of shelf sprinklers is the sprinkler protection cage and shield to prevent water from the sprinklers above the sprinkler’s heat detection equipment. If this water shield is not used, medium sprinklers will not be able to reach the required temperature.

Usage Areas
– Warehouses / Warehouses
– Large Stores
– Mass Storage
– Logistic Centers

Warehouse Type Sprinklers are divided into five within themselves.

– ESFR (Early Suppression Fast Response) sprinkler
– CMSA (Control Mode Specific Application) Sprinklers
– in CM (Control Mode Density Area) Sprinkler
– EC Storage (Extended Coverage) Sprinkler

ESFR (Early Suppression Fast Response) Sprinkler

ESFR sprinklers

ESFR sprinklers 3 differences compared to other sprinklers;

  • Speed  – ESFR sprinkler heads detect the fire according to other sprinklers and take up to half the time of starting the water flow.
  • Volume  – ESFR sprinklers throw water up to 100gpm while throwing water at 25-60gpm to other sprinklers.
  • Droplet size  – ESFR sprinkler heads perform water flow with larger droplets than other sprinklers.

 

ESFR – K: 14 (200)

Pendent
Connection Diameter: Pir Yüzey npt 
Mounting Type: Pendent Type
K-Factor: 14 (200)
Approvals: FM, UL, ULC, LPCB, VdS
Temperature: 74 ° C, 96 ° C
Surface: Brass
Sin: VK500

– ESFR (Early Suppression, Fast Response) A sprinkler in the extinguishing mode.
– It is heat sensitive thanks to Melt Solder.
– Designed for the protection of high storage with shelf and stack.
– Eliminates the use of sprinklers between shelf.

Upright


Upright sprinklers

Connection Diameter:: inç npt
Mounting Type: Upright Type (
K-Factor): 14 (200)
Approvals: FM, UL, ULC, LPCB, VdS
Temperature: 74 ° C, 96 ° C
Surface: Brass
Sin: VK520

– ESFR (Early Suppression, Fast Response) A sprinkler in the extinguishing mode.
– It is heat sensitive thanks to Melt Solder.
– Designed for the protection of high storage with shelf and stack.
– Eliminates the use of sprinklers between shelf.
– Unique, upright (vertical) type design with pendent sprinkler installation is not the only alternative alternative.

ESFR – K: 17 (242)  Pendent

ESFR - K: 17 (242) Pendent Sprinkler
Connection Diameter:: inç npt
Mounting Type: Pendent Type
K-Factor: 16.8 (242)
Approvals: FM, UL, ULC, LPCB, VdS
Temperature: 74 ° C, 96 ° C
Surface: Brass
Sin: VK503

– ESFR (Early Suppression, Fast Response) A sprinkler in the extinguishing mode.
– It is heat sensitive thanks to Melt Solder.
– Designed for the protection of high storage with shelf and stack.
– Eliminates the use of sprinklers between shelf.
– ESFR requires a lower pressure than K: 14.

ESFR – K: 22.4 (320) Pendent

ESFR - K: 22.4 (320) Pendent Sprinkler

Connection Diameter: 1 Sin npt
Mounting Type: Pendent Type
K-Factor: 22.4 (320)
Approvals: FM, UL, ULC, LPCB, VdS
Temperature: 74 ° C, 96 ° C
Surface: Brass
Sin: VK506

– ESFR (Early Suppression, Fast Response) A sprinkler in the extinguishing mode.
– It is heat sensitive thanks to Melt Solder.
– Designed for the protection of high storage with shelf and stack.
– Eliminates the use of sprinklers between shelf.
– It requires lower pressure than ESFR K: 17.

ESFR – K: 25 (363) Pendent

ESFR - K: 25 (363) Pendent Sprinkler

Connection Diameter: 1 Sin npt
Mounting Type: Pendent Type
K-Factor: 25 (363)
Approvals: FM, UL, ULC, LPCB, VdS
Temperature: 74 ° C, 96 ° C
Surface: Brass
Sin: VK510

– ESFR (Early Suppression, Fast Response) A sprinkler in the extinguishing mode.
– It is heat sensitive thanks to Melt Solder.
– Designed for the protection of high storage with shelf and stack.
– Eliminates the use of sprinklers between shelf.
– Requires lower pressure than ESFR K: 22.4.

CMSA (Control Mode Specific Application) Sprinkler

HIGH CHALLENGE® LARGE DROP UPRIGHT SPRINKLER K: 11.2 (160)

HIGH CHALLENGE® LARGE DROP UPRIGHT SPRINKLER

Connection Diameter: ½ ° npt – 93 C npt
Mounting Type: Upright Type
K-Factor: 11.2 (160)
Approvals: FM, UL, ULC
Temp: 68 ° C, 93 ° C, 141 ° C
Surface: Brass
Sin : VK540

– Heat sensitive with 5mm Glass Finder.
– High Challenge Large Drop Sprinkler Group A is designed for the protection of warehouses between shelf fires without using sprinklers between the shelf (storage height 7,6 m floor height up to 9,1 m).
– The distance between the deflector of the sprinkler and the top of the last pallet shall not be less than 914mm.

STANDARD RESPONSE CMSA PENDENT SPRINKLER K: 19.6 (282.6)

STANDARD RESPONSE CMSA PENDENT SPRINKLER

Connection Diameter: 1 Sin npt
Mounting Type: Pendent Type
K-Factor: 19.6 (282.6)
Approvals: FM, UL, ULC
Temp: 71 ° C, 96 ° C
Surface: Brass
Sin: VK592

– It is heat sensitive thanks to Melt Solder.
– Standard Response CMSA Pendent Sprinkler Group A is designed for the protection of warehouses between shelf fires up to plastic without using sprinklers (storage height up to 7.6m high height up to 10.6m).
– The distance between the deflector of the sprinkler and the top of the last pallet shall not be less than 914 mm.

CMDA (Control Mode Density Area) Sprinkler

UPRIGHT SPRINKLER (STORAGE-DENSITY / AREA) K: 16.8 (242)

UPRIGHT SPRINKLER (STORAGE-DENSITY / AREA)

Connection Diameter: Yüzey ° npt
Mounting Type: Upright Type (Vertical) Type
K-Factor: 16.8 (242)
Approvals: FM, UL, ULC
Temperature: 68 ° C, 79 ° C, 93 ° C, 141 ° C
Surface: Brass
Sin : VK580

– Heat sensitive with 5mm Glass Finder.
– Due to the low pressure requirement, a lower pipe diameter, lower pump capacity, lower water tank and thus a more economical solution are produced.
– Large orifice sprinklers are designed for use in high density storage.
– It’s a standard response sprinkler.

ELO sr UPRIGHT / pendent SPRINKLER (STORAGE-DENSITY / AREA) K: 11.2 (160)

ELO sr UPRIGHT / pendent SPRINKLER (STORAGE-DENSITY / AREA)

Connection Diameter: °, npt
Mounting Type: Upright (Pendent) Type
K-Factor: 11.2 (160)
Approvals: FM, UL, ULC
Temp: 68 ° C, 79 ° C, 93 ° C, 141 ° C
Surface: Brass, Chrome, White and Black
Sin: VK530 / VK536

– Heat sensitive with 5mm Glass Finder.
– It’s a standard response sprinkler.
– Extra Large orifice sprinklers are designed for use in high density storage and manufactures.
– Due to the low pressure requirement, a lower pipe diameter, lower pump capacity, lower water tank and thus a more economical solution are produced.
– It can be used as an intermediate level sprinkler when used with sprinkler protection cage and shield.

ELO qr UPRIGHT / pendent SPRINKLER (STORAGE-DENSITY / AREA) K: 11.2 (160)

ELO qr UPRIGHT / pendent SPRINKLER

Connection Diameter: °, npt
Mounting Type: Upright (Pendent) Type
K-Factor: 11.2 (160)
Approvals: FM, UL, ULC
Temp: 68 ° C, 79 ° C, 93 ° C, 141 ° C
Surface: Brass, Chrome, White and Black
Sin: VK531-533 / VK377

– 3mm Glass Finder (VK531-VK377) is heat sensitive as a solder (VK533).
– Quick-action sprinklers.
– Extra Large orifice sprinklers are designed for use in high density storage and manufactures.
– Due to the low pressure requirement, a lower pipe diameter, lower pump capacity, lower water tank and thus a more economical solution are produced.
– It can be used as an intermediate level sprinkler when used with sprinkler protection cage and shield.

EC Storage (Extended Coverage) Sprinkler

EXTENDED COVERAGE UPRIGHT SPRINKLER (STORAGE-DENSITY / AREA) K: 25.2 (363)

EXTENDED COVERAGE UPRIGHT SPRINKLER

Connection Diameter: ½ inç npt
Mounting Type: Upright Type (Vertical) Type
K-Factor: 25.2 (363)
Approvals: FM, UL, ULC
Temp: 74 ° C, 101 ° C
Surface: Brass
Sin: VK595

– It is heat sensitive with melting solder.
– Wide shielded sprinklers are suitable for use in areas designed for high danger and high density storage area based on area / density principle with lower pressure requirement.
– The distance between the deflector of the sprinkler and the top of the last pallet shall not be less than 914mm.